CÀI ĐẶT THÔNG SỐ BIẾN TẦN ABB CHO ỨNG DỤNG LÒ HƠI
Cài Đặt Thông Số Biến Tần ABB Cho Ứng Dụng Lò Hơi
- 19.11 ext1/ext2 selection DI3
- 20.06 Ext2 commands ín1 start, ìn2 dir
- 20.08 Ext2 in1 source DI1
- 21.03 Stop mode Ramp
- 28.11 Ext1 frequency fef1 AI2 scaled
- 28.15 Ext2 frequency ref1 AI1 scaled
- 28.22 Constant frequency sel1 : always off
- 28.72 Freq acceleration time 1 60.000s
- 28.73 Freq deceleration time 1 90.000s
Ứng dụng có sử dụng truyền thông
- 58.01 Protocol enable Modbus RTU
- 58.03 Node address 1
- 58.15 Communication loss mode Cw/Ref1/Ref2
- 58.16 Communication loss time 15.0
- 58.28 EFB act1 type Transparent
- 58.29 EFB act2 type Transparent
- 58.31 EFB act1 transparent source P.1.6
- 58.32 EFB transparent source P.1.7
- 58.107 Data I/O 7 1.11[16]
- 58.108 Data I/O 8 1.13 [16]
- 58.109 Data I/O 9 1.14 [16]
- 58.110 Data I/O 10 1.7 [16]
- 58.111 Data I/O 11 1.31 [16]